For a factory it means smooth, cleanable, non-absorbent surfaces without open joints; natural ventilation openings of at least 5% of the floor area or mechanical ventilation to the building regulations; daylight openings of at least 10% of the floor area or lighting of at least 200 lux with protected fittings; hot and cold water, hand-washing with soap and disposable drying, toilets and basins in set numbers, a changing area, approved waste-water and refuse arrangements; food-contact equipment that is smooth and non-toxic and, after cleaning, carries no more than 100 viable micro-organisms per square centimetre; and temperature control with thermometers.

Regulations change. Confirm the current requirement with the authority named in each section before you commit money.

The requirements at a glance

AreaWhat R638 requiresRegulation
Walls, floors, ceilingsSmooth, rust-free, non-toxic, cleanable, non-absorbent, dust-proof, water-resistant, no open joints5(3)(a)
VentilationNatural openings at least 5% of the floor area, or artificial ventilation meeting the National Building Regulations5(3)(b)(i)
LightingDaylight openings at least 10% of the floor area, or artificial lighting of at least 200 lux with fittings protected against glass contamination5(3)(b)(ii)
Water and cleaningWash-up facility with hot and cold water; adequate water supply5(3)(c), (d)
PestsPest proof; effective control of flies, cockroaches and other insects5(3)(c)
WasteWaste-water disposal system and controlled refuse area approved by the local authority; lidded refuse containers; area to clean them5(3)(c), (d)
Sanitary facilitiesToilets, urinals and hand basins in the numbers in Annexure D5(3)(d)
Hand-washingWith hot water where possible, soap and disposable drying or equivalent5(3)(d)
ChangingSeparate changing area with clothing storage5(3)(d)
SeparationNo direct connection between food rooms and contaminating areas; toilets only via a ventilated lobby or self-closing door with negative-pressure extraction5(3)(e), (f)
Food-contact surfacesSmooth, rust-proof, non-toxic, non-absorbent, no open joints6(1)
Cleanliness of surfacesAfter cleaning, not more than 100 viable micro-organisms per cm² on analysis6(4)
TemperatureChillers, freezers and heated holding fitted with thermometers; foods in Annexure E kept at specified core temperatures6(5), 8(4)
PeoplePerson in charge and staff trained in food safety and hygiene, with records10

Building and finishes

Food-handling areas need surfaces that can be cleaned and do not harbour dirt: smooth, non-absorbent, water-resistant walls and floors without open joints or seams. In food-serving and storage areas, face brick or properly jointed walls and easy-to-clean decorative finishes are allowed, but processing rooms need the full standard. For a factory this usually means sealed or epoxy floors with falls to drains, hygienic wall panels or sealed plaster, and coved junctions.

Ventilation and lighting

R638 gives two routes for each:

  • Ventilation: natural openings to the outside air of at least 5% of the room's floor area, positioned for cross-ventilation; or artificial ventilation that complies with the National Building Regulations and removes steam, vapours, warm air and contaminants.
  • Lighting: transparent surfaces admitting daylight of at least 10% of the floor area; or artificial lighting complying with the building regulations, of at least 200 lux, with intensity suited to the work and fittings protected so that broken glass cannot reach food.

Processing rooms with ovens, fryers, kettles or retorts almost always need mechanical extraction.

Water, washing and waste

Every food premises needs a wash-up facility with hot and cold water and an adequate water supply. Hand-washing facilities must have hot water where possible, soap or another cleaning agent, and disposable towels or a hand drier. Waste water must go into a system approved by the local authority, and refuse needs lidded, liquid-proof containers and a separate area where the containers are stored and cleaned.

Toilets, changing and separation

Annexure D of R638 sets the number of toilets, urinals and hand basins by headcount. Separate facilities for men and women are not needed where only one sex works on the premises or no more than ten people work there. Workers need a separate changing area with storage for clothes. Food rooms may not connect directly to areas with fumes, dust or odours, and may connect to a toilet only through a ventilated lobby, or through a self-closing door where the toilet has mechanical extraction keeping it under negative pressure.

Equipment and food-contact surfaces

Tables, counters and equipment that touch food must be smooth, rust-proof, non-toxic and non-absorbent, without open joints or seams; wooden chopping boards are allowed if kept clean. Surfaces must be cleaned before first use and as often as needed during and after processing, and after cleaning must not carry more than 100 viable micro-organisms per square centimetre on analysis. Single-use items are used once.

For machinery this translates into stainless or food-grade food-contact parts, welds ground smooth, no dead legs in pipework, and designs that can be stripped or cleaned in place.

Temperature control

Chillers, freezers and heated holding equipment must have thermometers that show the temperature accurately. Foods listed in Annexure E must be kept, during storage, transport and display, at core temperatures not above (for chilled and frozen foods) the specified values; chilled or frozen food may not be sold if its surface is more than 2 °C warmer than the required core temperature. Food sold directly to consumers within four hours of preparation is exempt from this rule.

Milk heat-treatment equipment must have dial thermometers and thermostats accurate to 0.5 °C, time and temperature regulators and alarms, and flow-diversion valves that send under-treated milk back to the balance tank.

Duties of the person in charge

The person in charge must be trained in food safety and hygiene, ensure staff are trained, keep training records available to inspectors, control pests, and manage refuse. A food factory therefore needs procedures and records as well as compliant buildings and equipment. Many buyers also expect a HACCP-based food safety system; the HACCP regulations (R908 of 2003) set out how such a system is applied where required.

What must go on the pack: see food labelling regulations under R146.

Discharging process wastewater? See the trade effluent permit for a food factory.

What to ask equipment suppliers

  • Are all food-contact parts stainless or food-grade, with smooth welds and no crevices?
  • How is each machine cleaned, how long does it take, and can it be cleaned in place?
  • Where do drains, hand-wash points and cleaning access sit in the layout?
  • Do chillers, freezers, ovens and heat-treatment units have accurate thermometers and recording?
  • For milk: does the pasteuriser have flow diversion and 0.5 °C accurate instruments?
  • Does the layout separate raw and finished product flows?

Common misconceptions

  • "Stainless steel is enough." Design for cleaning matters as much as the material.
  • "We will fix the building later." The inspector looks at the building first.
  • "Small premises are exempt." R638 applies to all food premises; only specific exemptions under regulation 14 apply.
  • "The equipment supplier handles compliance." Compliance is the responsibility of the person in charge; suppliers provide equipment and layouts that make it possible.

Where CISH fits

CISH designs, supplies, installs and commissions food production lines from audited factories in China, with equipment and layouts chosen so that the premises can meet R638: cleanable food-contact surfaces, clean and dirty flows, hand-wash and drainage points, and temperature instruments. The certificate is applied for by the person in charge; see our Certificate of Acceptability guide for the process.

Frequently asked questions

What is R638 in South Africa?

The regulations governing general hygiene requirements for food premises, the transport of food and related matters, published as R638 on 22 June 2018 under the Foodstuffs, Cosmetics and Disinfectants Act. They apply to all food premises.

What lighting does a food factory need under R638?

Either daylight openings of at least 10% of the floor area, or artificial lighting meeting the building regulations of at least 200 lux, with fittings protected against glass contamination.

What ventilation does R638 require?

Natural openings of at least 5% of the floor area allowing cross-ventilation, or artificial ventilation meeting the National Building Regulations that removes steam, vapours and contaminants.

How clean must food-contact surfaces be?

After cleaning, not more than 100 viable micro-organisms per square centimetre on analysis.

Do I need separate toilets for men and women?

Not where only one sex works on the premises or no more than ten people work there; otherwise the numbers in Annexure D apply.

Does R638 apply to small food businesses?

Yes. It applies to all food premises, with specific exemptions only under regulation 14.

Does CISH make premises R638 compliant?

We design and equip production lines so that premises can comply. Compliance and the certificate are the responsibility of the person in charge.